Product Configuration
- F3 Approval: FM XP, NI, DIP I, II, III/1+2/A-G
- A Communication; Output Signal: HART; 4-20 mA, 2 channel
- 2 Electrical Connection: Screw terminals, housing form B, DIN EN 50446
- G Field Housing: TA30H; 2x 1/2NPT; glass display window, explosionproof enclosure
- B1 Configuration Universal Input: Ch1: RTD 3-wire, Ch2: inactive
- A1 Sensor Type Input 1: Pt100, -200...850oC, min. span 10K, IEC60751 (a = 0.00385)
- AA Sensor Type Input 2: Inactive
- A1 Input; Interconnection: PV = CH1; CH2 inactive
- PA >>Accessory Enclosed: Mounting bracket wall, 316L
Product Highlights
- Certified up to SIL 2/3 - hardware/software - according to IEC 61508:2010
- Safe operation in hazardous areas, international approvals such as FM IS, NI; CSA IS, NI; ATEX, NEPSI, IECEx Ex ia, Ex nA for intrinsically safe installation in zone 1 and zone 2
- HART® 7 version
- High accuracy of measuring point through sensor-transmitter matching
- Reliable operation with sensor monitoring and device hardware fault recognition
- Diagnostics information according to NAMUR NE107
- Rapid no-tools wiring due to optional spring terminal technology